Electrical data
| Number of devices parallel connection max. |
5 |
| Number of devices series connection max. |
2 |
| Parallel connection |
yes |
| Series connection |
yes |
| Security level |
SELV |
Electrical data | Supply
| Power frequency |
50 ... 60 Hz |
Electrical data | Input
| Input voltage AC min. |
360 V |
| Input voltage AC max. |
550 V |
| Input current AC (3-phase) |
0,33 A |
| Inrush current max. |
15 A |
| External back-up fuse per phase max. |
2 A |
| Phase number input |
3 |
| Efficiency |
90 % |
Electrical data | Output
| Selectable switch-off mode |
front sided plug link (automatic re-start or definite shut-off) |
| Output voltage DC |
24 V |
| Output voltage DC min. |
24 V |
| Output voltage DC max. |
28 V |
| Output voltage adjustable |
yes |
| Output current |
5 A |
| Output current (UL) |
6 A |
| Mains failure bridging min. |
25 ms @ 400 V AC |
| Ripple effective max. |
20 mV |
| Spikes (s-s) max. |
100 mV |
Device protection | Electrical
| Overload protection output |
yes |
| Short-circuit protection output |
yes |
Mechanical data | Mounting data
| Mounting method |
geschnappt |
| Suitable for mounting type |
Mounting rail TH35, (EN 60715) |
| Height |
127 mm |
| Width |
68 mm |
| Depth |
198 mm |
Environmental characteristics | Climatic
| Operating temperature min. |
0 °C |
| Operating temperature max. |
60 °C |
| Storage temperature min. |
-25 °C |
| Storage temperature max. |
85 °C |
| Relative humidity min. (operation) |
5 % |
| Relative humidity max. (operation) |
95 % no condensation |